Load has the seventh highest operating priority. Only from F-Stop or Unload states. Normal operation is
from F-Stop with the dancer in the full position. Load can also be initiated from Unload state with positive
Dancer Error. Load has a ten second (10s) timer. If the Dancer is not loaded within 10 seconds after the Load
input is latched the CX-1102 automatically reverts to the F-Stop operating state. The Load input may be held
closed to keep the CX-1102 from changing to F-Stop and therefore complete the Load.
To activate Load:
Activate Low (closed to common), Level Sensitive, Latched
Use momentary contact - does not need to be maintained to remain active
Figure 36 Load Input
Load
Run
Commo
n
F-Stp
UnLd
H-Stp
Commo
n
Run
Close Momentarily
5
6
8
1
2
4
3
J6
H-Stop
F-Stop
Unload
Load